Dry-Season Camp Fires: Which Pump and Hose to Keep Ready

By Tony Miller7 min read

A grass fire burning through dry grassland and bare shrubs, with smoke drifting through the trees

A camp facing dry-season fires needs a portable high-pressure fire pump, enough lay-flat hose to reach the far side of every block, and a reserve of water that nobody draws for drinking. Station the pump where the crew can reach it in minutes, keep it fuelled, and drill the crew weekly until the rains return.

Why do camp fires peak in the dry season?

In South Sudan the rains run on average from April to October (Evidence on Demand helpdesk report on seasonality in South Sudan, GOV.UK). Once they stop, grass, thatch, plastic sheeting and stored firewood dry out, and cooking fires sit a few metres from walls that burn in seconds. The same report notes that dry-season water sources are depleted and water points become congested. So fire risk rises at exactly the moment water is hardest to find.

What do the camp standards say about fire?

The Sphere Handbook sets the layout rules that make a pump useful. Fire risk assessments should inform site planning, built-up areas of camps should have 30-metre firebreaks every 300 metres, and buildings should stand at least 2 metres apart, ideally double the building height. Sphere also asks responders to consider fire safety equipment, awareness training, and telling residents about fire prevention and evacuation plans (Sphere Handbook 2018, Shelter and Settlement, p. 252).

CCCM Cluster fire safety guidance goes further on equipment. It asks for a fire assessment that sets the type and number of extinguishers, other means such as sand and water hose stations, assembly points and road access for firefighting vehicles, and for trained community firefighting committees (CCCM Cluster, Guidelines for Fire Safety in Formal and Informal Settlements).

Which fire pump suits a camp?

A camp needs pressure more than volume. The job is to push water through a long, thin hose and still have a useful jet at the nozzle. A trash or dewatering pump moves a lot of water at low pressure, so it is the wrong tool for the hose end, though it is the right tool for refilling the reserve tank.

The Aussie Pumps fire pump range that SLS supplies is built for this. The figures below are from the manufacturer’s petrol fire pump spec sheet (Aussie Pumps, petrol drive fire fighting pumps).

ModelEngineMax headMax flowBest camp role
Fire Chief QP205SEHonda GX160, 5.5 HP75 m450 L/minLight, on skids: a block or zone pump carried to the fire
Fire Captain QP205SHonda GX160, 5.5 HP75 m450 L/minSame pump in a full roll frame, better for rough handling
Fire Captain Plus QP205SLHonda GX200, 6.5 HP75 m450 L/minMore engine margin for long hose lays
Mr T twin impeller QPT-205SLTHonda GX270 or GX390, 9 or 13 HP95 m500 L/minCentral pump for the longest runs and highest pressure

Other points from the same spec sheet matter in a camp. All four models self-prime from 7.6 metres, carry a five-year pump end warranty, and use a three-way outlet so you can run 1 inch or 1.5 inch lines. The 13 HP electric start Mr T can take an 18 litre long-range fuel tank and run for up to 4.5 hours under load. Diesel drive (Yanmar, Kubota or Hatz) is also made if your site holds no petrol.

A simple rule of thumb: one light pump per zone between firebreaks, plus one high-pressure central pump at the main water point. If the site runs on diesel only, ask for the diesel versions rather than adding a petrol supply chain just for fire.

How much hose do you need?

Measure from where the pump will stand to the farthest shelter it must protect, then add a margin for walking the hose around corners and fences. On a Sphere grid with firebreaks every 300 metres, a pump stationed on a firebreak may need to reach about 150 metres into the block (estimated: 300 m ÷ 2). With 20 metre lengths, that is eight lengths per pump (estimated: 150 ÷ 20 = 7.5, rounded up). Aussie Pumps sells a deluxe hose kit with two 20 metre delivery hoses and nozzles, plus Storz fittings and a coupling kit (Aussie Pumps spec sheet, optional accessories), so plan for extra lengths beyond the kit.

Every extra metre of hose costs pressure. Aussie Pumps’ own golden rule is to operate the pump at its best efficiency point, about 85% of maximum head (Aussie Pumps spec sheet). For the longest lays, pick the higher-head model rather than hoping a smaller one will cope. Test the full lay during a drill: if the jet at the nozzle is weak, shorten the run or move the pump point.

  • Couplings: one coupling standard across the whole site, so any hose fits any pump.
  • Suction: a hard suction hose and strainer for each pump; soft hose collapses under suction.
  • Storage: hose rolled, dry and out of the sun, with a spare length for every four in use.

How much water should you hold for firefighting?

Hold a dedicated fire reserve that is never drawn for drinking or washing. If the fire water sits in the same tank as the supply, it will be gone by the afternoon queue.

Size it against the pump. A Fire Chief at its maximum 450 litres a minute would empty a 10,000 litre reserve in about 22 minutes (estimated: 10,000 ÷ 450). At working pressure the flow is lower, so the tank lasts longer, but the arithmetic shows why a small tank buys only one short attack. One workable layout pairs a raised Oxfam steel tank at the main water point with smaller filled drums or bladders at each firebreak. For the drinking-water side of the calculation, see how much water storage a camp needs, then add the fire reserve on top.

Refill the reserve the same day it is used. A 4 or 6 inch Multiquip trash pump does this job well from a river or khor while the water lasts; the fire pump then draws from the tank.

How should the crew drill before the dry season?

Equipment without a trained crew is a pump in a container. The CCCM Cluster guidance calls for community committees, trained by a specialist team, that fight a fire until the fire brigade arrives, guide residents to assembly points and give first aid (CCCM Cluster fire safety guidelines). A workable routine:

  1. Name the crew. Pick a team for each pump, with a leader and deputies, and post the names at the pump point.
  2. Start every pump weekly. Check oil, fuel and the suction strainer, prime it and run it briefly. If a pump will not draw, work through priming and suction lift before the day you need it.
  3. Lay the full hose monthly. Run it from the pump point to the farthest shelter, charge it, and check pressure at the nozzle.
  4. Time the response. Record how long it takes from alarm to water on target, and fix what slows it down.
  5. Walk the evacuation route. Rehearse moving residents to the assembly point, including people with limited mobility, as Sphere asks.
  6. Log and restock. Refill fuel and the fire reserve, dry and roll the hose, and note any damaged lengths for replacement.

Where can you read more on Aussie Pumps?

For the wider case for Aussie Pumps in South Sudan’s heat and dust, read why Aussie Pumps suit South Sudan, and for how Aussie and Multiquip pumps fit together on one site, see our guide to Aussie Pumps and Multiquip solutions.

Frequently asked questions

Can a trash pump be used to fight a fire?

Only as a last resort. A trash pump is built to move large volumes of dirty water at low pressure, so at the end of a long hose it gives a weak stream. A dedicated fire pump such as the Aussie Fire Chief reaches heads of up to 75 metres. Use the trash pump to refill the fire reserve and the fire pump to put water on the fire.

How far apart should firebreaks be in a camp?

The Sphere Handbook recommends 30-metre firebreaks every 300 metres in built-up areas of camps, with at least 2 metres between buildings and ideally double the building height. That grid decides where fire pumps and water reserves should stand: on the firebreaks, so a crew can reach any shelter in its zone with the hose it holds.

Petrol or diesel fire pump for a camp?

Match the fuel your site already holds. Aussie fire pumps come with Honda petrol engines as standard, and the manufacturer also makes diesel drive versions with Yanmar, Kubota or Hatz engines. If generators and vehicles on site run on diesel, a diesel fire pump avoids storing petrol just for fire, which is one less supply line and one less fire hazard.

How often should a camp fire crew drill?

A sensible routine is a weekly start-up check of every pump and a monthly full drill that lays the hose to the farthest shelter, charges it and times the response. Run a full drill before the dry season starts and again whenever crew members change. Record each drill so problems with priming, hose or fuel are fixed before a real fire.

To get a quotation for fire pumps, hose and storage for your site, email sales@maji-safi.org, WhatsApp +254 722 824 480, or use the SLS quotation form.